Commercial Fire Door Inspections & Surveys
Fire doors are one of the most critical life safety features in any commercial or public building. They prevent the spread of lethal smoke and flames, protect escape routes, and buy vital evacuation time. Delivered by The Handheld Fire Extinguisher Company Limited.
Why Compliant Fire Doors Are Essential
Without correctly fitted and fully operational fire doors, even a minor office or kitchen fire can rapidly penetrate escape corridors within minutes, cutting off stairwells and filling evacuation routes with toxic fumes.
Whether commissioned as part of your statutory Fire Risk Assessment or as an independent door register audit, we ensure your doors function as engineered barrier systems to protect lives, stock, and structural property.
Smoke Containment
Smoke inhalation causes over 50% of fire casualties in the UK. Certified cold-smoke seals prevent lethal carbon monoxide and particulates from blinding and incapacitating evacuees.
Compartmentation Integrity
Fire doors isolate hazards at the point of origin, stopping flashover transitions between rooms and preserving structural timbers and steelwork until the Fire Service arrives.
Understanding Fire Door Ratings
Fire doors are rigorously laboratory-tested to withstand fire for designated timeframes:
FD30 / FD30S Doors
Engineered to hold back flames and heat for a minimum of 30 minutes (the "S" denotes smoke seal fitted).
- Typical thickness: ~44mm solid core timber or composite.
- Commonly specified for commercial offices, low-rise residential flats, retail corridors, and hotel guestrooms.
- Fitted with intumescent perimeter strips that expand at 200Β°C to seal gaps.
FD60 / FD60S Doors
Provides a robust 60-minute barrier against severe thermal radiation, intense heat, and high fire loading.
- Typical thickness: ~54mm heavy-density core with specialized intumescent ironmongery bedding.
- Mandatory for boiler rooms, plant rooms, commercial kitchens, multi-storey protected stair enclosures, and hospitals.
- Ensures vital evacuation margins for vulnerable occupants with delayed egress needs.
Our Pragmatic Inspection Approach
We balance complete regulatory compliance with commercial sense, protecting both your safety and budget:
Risk-Based Evaluation
We evaluate operational suitability rather than instantly recommending costly full-frame door replacements where minor remedial servicing suffices.
Intumescent & Smoke Seals
Verification that heat-activated intumescent seals and draught smoke brushes are continuous, undamaged, and correctly sized in the frame rebate.
Gap & Tolerance Gauge Checks
Precision measurement using BS 8214 gap gauges to verify the perimeter gap does not exceed 3mmβ4mm and threshold clearance meets code.
Self-Closing Mechanisms
Testing overhead overhead door closers and floor springs to ensure doors latch fully into the frame without sticking or requiring manual force.
Certified Ironmongery & Glass
Checking CE/UKCA stamped fire-rated hinges, intumescent hinge pads, latch mechanisms, and certified wired/pyrostop vision panels.
Auditable Asset Register
Each door is tagged and logged in a clear compliance report, detailing pass/fail status, photos, and itemised minor remedial actions.
The 5 Core Checks Every Dutyholder Should Conduct
Under the Fire Safety (England) Regulations 2022, building owners and facilities managers must carry out regular visual inspections of fire doors. If any door fails these 5 checkpoints, professional servicing is required:
1. Certification & Plugs
Look at the top edge of the leaf. A coloured plug or certification label (e.g., BM TRADA Q-Mark, Certifire) proves it is a certified fire door assembly.
2. Perimeter Gaps (3mm - 4mm)
Gaps around the top and sides must consistently sit between 3mm and 4mm (about the thickness of a Β£1 coin). Underneath, threshold gaps should be under 8mm (or 3mm for smoke control).
3. Seals (Intumescent & Smoke)
Check that intumescent strips running down the door edge or frame rebate are well-fitted, continuous, free from paint covering, and not torn or missing.
4. Hinges & Fasteners
Doors must be hung on at least 3 fire-rated steel hinges (bearing the CE/BS EN 1935 mark). Check that all screws are firmly in place with no dark oil leaks.
5. Full Latching & Closure (Never Wedge Open!)
Open the door to approximately 75mm (halfway), let go, and verify it firmly closes and latches into the frame on its own. Fire doors must never be held open with timber wedges or fire extinguishers.
Book A Fire Door Compliance Survey
Tell us about your building and our Hitchin survey team will respond within 24 hours with an itemised quotation.
Book A Fire Door Survey
Speak with our compliance surveyors in Hitchin on 07359 728193 or submit below:








